8. PARAMETER DESCRIPTION
IMR02C15-E4
8-41
PV bias
Factory default setting:
The screen is displayed.
PV bias adds bias to the Measured value (PV). The PV bias is used to
compensate the individual variations of the sensors or correct the difference
between the Measured value (PV) of other instruments.
Data range Factory set value
TC/RTD input:
−1999 (−199.9) to +9999 (+999.9) °C [°F]
Voltage (V)/Current (I) input:
−Input span to +Input span
0 (0.0)
PV bias is not displayed when the block selection at F09 [S.F09] (P. 8-85)
is set to “1: No display” in the Engineering mode.
Related parameters
Engineering mode:
• PV bias (P. 8-84)
PV digital filter
Factory default setting:
The screen is displayed.
The PV filter is used to eliminate noise against the measured input.
Data range Factory set value
0 to 100 seconds
(0: Unused)
1
PV digital filter is not displayed when the block selection at F09 [S.F09]
(P. 8-85) is set to “1: No display” in the Engineering mode.
Related parameters
Engineering mode:
• PV digital filter (P. 8-84)