8. PARAMETER DESCRIPTION
IMR02C15-E4
8-42
Manual manipulated output value (MV)
Factory default setting:
The screen is not displayed.
Setting Manipulated output value (MV) in Manual (MAN) mode.
Data range Factory set value
PID control:
Output limiter low to Output limiter high
Heat/Cool PID control:
−Cool-side output limiter (high) to +Heat-side
output limiter (high)
0.0
Manual manipulated output value (MV) is not displayed as the default
value of the block selection at F10 [S.F10] (P. 8-62) is set to “1: No
display” in the Engineering mode. To show the parameter, set the value
to “0: Display.”
When the instrument is in the Manual (MAN) mode, manual setting of
the Manipulated output value is available at SV setting mode (P. 8-8).
Related parameters
Engineering mode:
• Manual manipulated output value (MV) (P. 8-86)
M-MV