8. PARAMETER DESCRIPTION
IMR02C15-E4
8-59
Dummy
F00
RUN/STOP setting
RUN/STOP transfer is can be set in the Engineering mode state. Select RUN or
STOP and press the key.
Data range Factory set value
0: RUN
1: STOP (STOP lamp lights)
0
Set RUN mode “0: RUN” prior to transfer RUN/STOP mode by digital
input (DI).
Relations between key operations/communication and DI status
Mode select from key operation or
communication
DI-switched * Actual state
RUN (Contact closed) RUN
RUN
STOP (Contact open)
RUN (Contact closed)
RUN/STOP transfer
or
RUN/STOP setting
STOP
STOP (Contact open)
STOP
* When digital input (DI) is used for transfer, the new state is not backed up to EEPROM.
RUN/STOP setting links to the operation by key. When RUN/STOP
mode is transferred by key, the set data of RUN/STOP setting is also
transferred.
R/S
SET
R/S
R/S