EasyManua.ls Logo

RKC INSTRUMENT RB Series - Page 223

RKC INSTRUMENT RB Series
306 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8. PARAMETER DESCRIPTION
IMR02C15-E4
8-99
Dummy
F33
Transmission output scale high
Transmission output scale low
Use to set a scale high limit value or low limit value of the Transmission output.
Data range Factory set value
Transmission output scale high
When MV1 is selected:
Transmission output scale low to +105.0 %
When PV or SV is selected:
Transmission output scale low to Input scale high
High-limit value of
input span
Transmission output scale low
When MV1 is selected:
5.0 % to Transmission output scale high
When PV or SV is selected:
Input scale low to Transmission output scale high
Low-limit value of
input span
The Decimal point position is the same as Decimal point position (PGdP)
of the input.
Related parameters
Engineering mode:
Output action at STOP mode (P. 8-96)
Transmission output type (P. 8-98)
AO full scale adjustment value, AO zero point adjustment value (P. 8-100)
Description of function
This is a scaling of the output range of the transmission content selected by the Transmission output
type (Ao).
Example: If scaling is made under the following conditions:
Output signal type: Current output 4 to 20 mA DC Transmission output scale high (AHS): +1372 °C
Transmission output type (Ao): Measured value (PV) Transmission output scale low (ALS): 200 °C
Measured value (PV)
20 m
A
4 m
A
200 °C +1372 °C
Current output
For the setting example of Transmission output, refer to 7.3 Transmission Output Function
(P. 7-12).
AHS
ALS