8. PARAMETER DESCRIPTION
IMR02C15-E4
8-100
Dummy
F33
AO full scale adjustment value
AO zero point adjustment value
To correct error between instruments, set AO full scale/Zero point adjustment
value.
Data range Factory set value
−10.0 to +10.0 %
Adjustment value
Do not change the factory set adjustment value for the AO full scale
adjustment value and or the AO zero adjustment value as the
accuracy will be changed.
(Transmission output accuracy: ±0.3 % of span)
Related parameters
Engineering mode:
• Output action at STOP mode (P. 8-96)
• Transmission output type (P. 8-98)
• Transmission output scale high, Transmission output scale low (P. 8-99)
îš„ Description of function (output calibration)
AO full scale/Zero point adjustment value will correct the error between the output signal from the
instrument and the reading of other instrument.
For the setting example of Zero and Full scale points, refer to îš„ Output calibration (P. 7-13).
AOFS
AOZR

Table of Contents

Other manuals for RKC INSTRUMENT RB Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RKC INSTRUMENT RB Series and is the answer not in the manual?

RKC INSTRUMENT RB Series Specifications

General IconGeneral
BrandRKC INSTRUMENT
ModelRB Series
CategoryTemperature Controller
LanguageEnglish

Related product manuals