EasyManua.ls Logo

RKC INSTRUMENT RB Series - Page 239

RKC INSTRUMENT RB Series
306 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8. PARAMETER DESCRIPTION
IMR02C15-E4
8-115
Dummy
F41
Event 1 output action at input burnout
F42
Event 2 output action at input burnout
F43
Event 3 output action at input burnout
F44
Event 4 output action at input burnout
Use to select the output action of the Event 1 at input burnout.
Use to select the output action of the Event 2 at input burnout.
Use to select the output action of the Event 3 at input burnout.
Use to select the output action of the Event 4 at input burnout.
Data range Factory set value
0: Event output is not forcibly turned ON when
the burnout function is activated.
1: ON at over-scale; no action at underscale
2: ON at underscale; no action at over-scale
3: ON at over-scale or underscale
4: OFF at over-scale or underscale
0
Related parameters
Parameter setting mode
Event 1 set value (EV1) to Event 4 set value (EV4) (P. 8-20)
Event 1 set value (EV1) [high] to Event 4 set value (EV4) [high] (P. 8-20)
Event 1 set value (EV1’) [low] to Event 4 set value (EV4’) [low] (P. 8-22)
Engineering mode:
Event 1 type to Event 4 type (P. 8-101)
Event 1 hold action to Event 4 hold action (P. 8-110)
Event 1 differential gap to Event 4 differential gap (P. 8-113)
Energized/De-energized of Event 1 output to Energized/De-energized of
Event 4 output (P. 8-116)
Event 1 timer to Event 4 timer (P. 8-118)
Event 1 interlock to Event 4 interlock (P. 8-120)
Ebo1