Publication 1734-UM001D-EN-P - April 2008
134 Calibrate Your Analog Modules
4. From the General Parameters dialog, select Calibration at the Groups
pull-down.
5. Select your channel.
6. Click Calibration Command, and Apply.
7. Click the Download to Device button.
Both channel status indicators turn off.
8. Apply 0.0V to the input.
9. Click Accept Low Calibration.
This is the group
pull-down.