10-14 Serial Port Communications and Commands Date Code 20001006
SEL-351 Instruction Manual
The factory default passwords for Access Levels 1, B, and 2 are:
Access Level Factory Default Password
1 OTTER
B EDITH
2 TAIL
Access Level Attempt (Password Required)
Assume the following conditions: Password jumper = OFF (not in place), Access Level = 0.
At the Access Level 0 prompt, enter the ACC command:
=ACC <ENTER>
Because the Password jumper is not in place, the relay asks for the Access Level 1 password to be
entered:
Password: ? @@@@@@
The relay is shipped with the default Access Level 1 password “OTTER”. Enter the default
password:
Password: ? OTTER <ENTER>
The relay responds:
FEEDER 1 Date: 03/05/97 Time: 08:31:10.361
STATION A
Level 1
=>
The “=>” prompt indicates the relay is now in Access Level 1.
If the entered password is incorrect, the relay asks for the password again (Password: ?). The
relay will ask up to three times. If the requested password is incorrectly entered three times, the
relay closes the ALARM contact for one second and remains at Access Level 0 (“=” prompt).
Access Level Attempt (Password Not Required)
Assume the following conditions: Password jumper = ON (in place), Access Level = 0.