Date Code 20001006 Serial Port Communications and Commands 10-11
SEL-351 Instruction Manual
Access Level 2
When the relay is in Access Level 2, the relay sends the prompt:
=>>
Commands CON through SET in Table 10.6 are available from Access Level 2. For example,
enter the SET command at the Access Level 2 prompt to make relay settings:
=>>SET <ENTER>
While in Access Level 2, any of the Access Level 1 and Access Level B commands are also
available (commands 2AC through PUL in Table 10.6).
COMMAND SUMMARY
Table 10.6 alphabetically lists the serial port commands within a given access level. Much of the
information available from the serial port commands is also available via the front-panel
pushbuttons. The correspondence between the serial port commands and the front-panel
pushbuttons is also given in Table 10.6. See Section 11: Front-Panel Interface for more infor-
mation on the front-panel pushbuttons.
The serial port commands at the different access levels offer varying levels of control:
The Access Level 1 commands primarily allow the user to look at information only
(settings, metering, etc.), not change it.
The Access Level B commands primarily allow the user to operate output contacts or
change the active setting group.
The Access Level 2 commands primarily allow the user to change relay settings.
Again, a higher access level can access the serial port commands in a lower access level. The
commands are shown in upper-case letters, but they can also be entered with lower-case letters.