10-38 Serial Port Communications and Commands Date Code 20001006
SEL-351 Instruction Manual
The above listings are the factory default passwords for Access Levels 1, B, and 2. To change
the password for Access Level 1 to BIKE, enter the following:
=>>PAS 1 BIKE <ENTER>PAS 1 BIKE <ENTER>
Set
=>>
After entering new passwords, type PAS <ENTER> to inspect them. Make sure they are what
you intended, and record the new passwords.
Passwords may include up to six characters. Valid characters consist of: ‘A-Z’, ‘a-z’, ‘0-9’, ‘-’,
and ‘.’. Upper- and lower-case letters are treated as different characters. Examples of valid,
distinct passwords include:
OTTER otter Ot3456 TAIL 123456 12345. 12345-
If the passwords are lost or you wish to operate the relay without password protection, put the
main board Password jumper in place (Password jumper = ON). Refer to Tables 2.6 and 2.7 for
Password jumper information.
If you wish to disable password protection for a specific access level [even if Password jumper is
not in place (Password jumper = OFF)], simply set the password to DISABLE. For example
PAS 1 DISABLE disables password protection for Level 1.
SET Command (Change Settings)
The SET command allows the user to view or change the relay settings – see Table 9.1 in
Section 9: Setting the Relay.
VER Command (Show Relay Configuration and Firmware Version)
The VER command provides relay configuration information such as nominal current input
ratings. An example printout of the VER command for an SEL-351 Relay follows:
=>>VER <ENTER>VER <ENTER>
Partnumber: 03510T43533141X
Mainboard: 0351
Appearance: Horizontal, Connectorized
Data FLASH Size: 1024 KBytes
Analog Input Voltage (PT) : 260 Vac, delta-connected
Analog Input Current (CT) : 5 Amp Phase, 5 Amp Neutral
Extended Relay Features:
Base Model
SELboot checksum xxxx OK
FID=SEL-351D-R108-VM-Z002002-D20000….
SELboot-351-R101
If above information is unexpected. . .
contact SEL for assistance
=>>