Date Code 20001006 Serial Port Communications and Commands 10-27
SEL-351 Instruction Manual
OUT1 =TRIP
OUT2 =CLOSE
OUT3 =SV1T
OUT4 =0
OUT8 =0
OUT5 =0
OUT6 =0
OUT7 =0
OUT9 =0
OUT10 =0
OUT11 =0
DP1 =IN2
DP2 =52A
DP3 =0
DP4 =0
DP5 =0
DP6 =0
DP7 =0
DP8 =0
SS1 =0
Press RETURN to continue <ENTER><ENTER>
SS2 =0
SS3 =0
SS4 =0
SS5 =0
SS6 =0
ER =/51P + /51G + /OUT3
FAULT =51P + 51G
BSYNCH=52A
CLMON =0
BKMON =TRIP
E32IV =1
=>SHO G <ENTER>SHO G <ENTER>
Global Settings:
TGR = 180.00 NFREQ = 60 PHROT = ABC
DATE_F= MDY FP_TO = 15
LER = 15 PRE = 4 DCLOP = OFF DCHIP = OFF
IN1D = 0.50 IN2D = 0.50 IN3D = 0.50 IN4D = 0.50
IN5D = 0.50 IN6D = 0.50 IN7D = 0.50 IN8D = 0.50
EBMON = Y COSP1 = 10000 COSP2 = 150 COSP3 = 12
KASP1 = 1.2 KASP2 = 8.0 KASP3 = 20.0
=>SHO P <ENTER>SHO P <ENTER>
Port F
PROTO = SEL
SPEED = 2400 BITS = 8 PARITY= N STOP = 1
T_OUT = 15 AUTO = N RTSCTS= N FASTOP= N