Date Code 20001006 Firmware Versions A-3
SEL-351 Instruction Manual
Firmware Part/Revision No. Description of Firmware
SEL-351-x-R205-VM-Z001001-D19990827
SEL-351-x-R205-V0-Z001001-D19990827
SEL-351-x-R111-VM-Z001001-D19990827
SEL-351-x-R111-V0-Z001001-D19990827
These firmware differ from previous versions as
follows:
Fixed scaling problems with the directional elements
and fault locator associated with the SEL-351-2, -3,
and -4 Relays that have 300 V PTs.
Added the MB8A and MB8B serial port protocol
settings options for MIRRORED BITS protocol
operating on communication channels requiring an
eight bit data format
Expanded the setting range for the SYNCP
(synchronizing phase) setting to accommodate
compensation angle settings for synchronism check
Changed DNP mapping command so that it now
requests a confirmation before saving the map
modification
Corrected Loss-of-Potential V
1
unlatch threshold for
300 V input models.
Model SEL-0351xT; wye-connected voltages
Model SEL-0351x0/x1/xY; wye-connected voltages
Firmware R111 for upgrades of old hardware:
Model SEL-0351xT; wye-connected voltages
Model SEL-0351x0/x1/xJ; wye-connected voltages