OPERATING INSTRUCTIONS | Bulkscan LMS511 8014829/ZNC5/2017-06-06 | SICK
Subject to change without notice
82
APPENDIX
Telegram example Result
Readoutvariablecontinuously(massowrate):
Request: <STX>sEN mvMassFlow 1<ETX>
Reply: <STX>sEA mvMassFlow 1<ETX>
<STX>sSN mvMassFlow 43006666<ETX>
<STX>sSN mvMassFlow 43006E14<ETX>
<STX>sSN mvMassFlow 430063D7<ETX>
Request: <STX>sEN mvMassFlow 0<ETX>
Reply: <STX>sEA mvMassFlow 0<ETX>
Themassowrateisout-
put continuously until the
output is stopped using sEN
mvMassFlow 0 .
Write variable (tolerance against vibration):
Login: <STX>sMN SetAccessMode 03 F4724744<ETX>
Reply: <STX>sWA SetAccessMode 1<ETX>
Request: <STX>sWN parVibrationTolerance +20<ETX>
Reply: <STX>sWA parVibrationTolerance<ETX>
Log out: <STX>sMN Run<ETX>
Reply: <STX>sAN Run 1<ETX>
Write successful. The new
tolerance against vibration
is 20%.
Execute method (start maintenance mode):
Login: <STX>sMN SetAccessMode 03 F4724744<ETX>
Reply: <STX>sWA SetAccessMode 1<ETX>
Request: <STX>sMN BsMaintenance<ETX>
Reply: <STX>sAN BsMaintenance<ETX>
Log out: <STX>sMN Run<ETX>
Reply: <STX>sAN Run 1<ETX>
The Bulkscan switches to
the Maintenance operating
mode.
Write a read-only variable (total volume):
Request: <STX>sWN mvVolumeSum +1000<ETX>
Reply: <STX>sFA A<ETX>
Measured values are not
input parameters. An error
will be output.
Tab. 22: Telegram examples (CoLa-A)
13.1.2 Logging in to the sensor/Logging out of the sensor
TobeabletochangethecongurationoftheBulkscan(writevariablesandexecute
methods), the user must log in to the sensor with a valid user level and password.
FollowingcongurationoftheBulkscan,theusermustlogoutofthesensor.Thenew
congurationisthentransferredtothedevice.
Permissible commands: sMN
Method name Description Variable type Value range
SetAccessMode
Select user level. A valid user
level must be included in the
transmission. Otherwise the
Bulkscan rejects the command.
string 2: Maintenance person-
nel
3: Authorized client
4: Service
Hash value of the password
- main: B21ACE26h
- client: F4724744h
string 00000000h …
FFFFFFFFh
Run
Logging out of the sensor