LED signals
The following ve status LEDs are available on the PROFINET module:
LED Color Description Position
H1 Green Relay K1 picked up
LED H1 switches on when the controller has detected the
CLOSED position and the pulse generator ceases to output
pulses. The LED H1 is controlled by the basic module (signal
X200.11).
H1021 H1022
H1011 H1012
H1 H2
H3
H1301
H1302
H1300
H2 Green Relay K2 picked up
LED H2 switches on when the current distance of the door
to the OPEN position falls below 2 cm and the relay has
switched on. The LED H2 is controlled by the basic module
(signal X200.9).
H3 Green Valid incoming telegram
LED H3 is controlled by the basic module (signal X200.12),
and indicates the communication status. The LED ashes to
indicate incoming, valid telegrams. Each signal change
stands for such a telegram.
H1011 Green Port 1: LINK
H1012 Orange Port 1: ACT
H1021 Green Port 2: LINK
H1022 Orange Port 2: ACT
H1300 Green Power on
H1301 Red "Bus error" PROFINET communication disrupted
The H1301 LED ashes red in the event of a PROFINET com‐
munication error.
H1302 Red "Group error" internal communication disrupted
The H1302 LED ashes red in the event of an internal com‐
munication error.
Network structure/network topologies
The ATD430W IO device supports the star, line, tree and ring structure network topologies.
The IO device has an integrated switch for the line and ring structures. The MRP redundancy
process is used in the case of the ring structure. In this case, the IO device is the MRP client and
cannot be used as the redundancy manager (MRP manager). This must be provided for
separately in the network structure.
GSD le
The characteristic communication features of the ATD430W IO device are specied in the form
of an electronic device data sheet (device master data le, GSD le). The GSD le has been
certied by the ComDeC test center for PROFINET eld devices according to EN 61158 and
IEC 61784.