7.4 SITOP PSU8200 13A/36V 3-phase
SITOP PSU8200 13A/36V
Connecting SITOP PSU8200 on the ATD4xxW door control unit
Slot Function
X3
SELV
1 + Plus
2 FE Functional grounding
3 - Minus
7.4.1 Power supply requirements of SITOP PSU8200
NOTICE
SITOP PSU8200 may be used only as of rmware version ATD4xxW ≥ 1.04.
Fuse protection
An MCB according to EN 60898‑1, 8 A, C‑characteristic of the type SIEMENS: 5SY4108‑7 is to be
inserted into the supply network by the customer.
Ensure that the MCB is operated only within the permissible range. The miniature circuit breaker
must be installed in the vicinity of the SIDOOR control unit at a similar ambient air temperature.
Default topology
Only the SIDOOR controller may be connected to the SITOP PSU8200; additional loads are not
allowed. The spatial extension of the supply circuit used must be less than 30 m.
Power supply
7.4 SITOP PSU8200 13A/36V 3-phase
ATD4xxW for industrial applications
System Manual, 06/2022, A5E51901827B AA 259