Connecting and commissioning
10
10.1 Overview of safety and commissioning
WARNING
Dangerous electrical voltage!
When electrical devices are used, certain parts of them have to carry dangerous voltages.
Failure to observe the operating instructions can therefore lead to serious injuries or material
damage.
Observe the operating instructions.
WARNING
Risk of injury during commissioning
The door movements cannot always be externally controlled while the control unit is being
commissioned (in particular during the automatic determination of parameters). The light
barrier is not active during the learn run.
During the learn run, the force is > 75 N and the energy > 4 J.
An authorized person must therefore be posted near the door to ensure that no one else can
enter the vicinity of the door during commissioning.
WARNING
Veri󹪝cation of safety-relevant functions
The SIDOOR control unit is only a subsystem (incomplete machine). In general, the correct
parameter assignment of the SIDOOR control unit and the e󹪜ectiveness of the safety-relevant
functions must be checked at regular intervals by testing the safety-relevant functions during
commissioning and depending on the application.
Note
The motor temperature must not be below 0°C during the learn run, as otherwise the mass to
be moved will be incorrectly determined, and the opening and closing speed may lie in an
impermissible range.
ATD4xxW for industrial applications
System Manual, 06/2022, A5E51901827B AA 291