The pin assignment at slot X3 is as follows:
)(
;
See also
Contr
ollers (Page 33)
7.3.2 Installation
Requirements
The installation site must ful󹪝ll the following requirements:
Minimum clearance to surrounding parts: 1 cm
Flat mounting surface made of metal
Maximum distance from the power supply due to cable length:
Connecting cable input line (mains ⇔ transformer): 200 cm
Connecting cable output line (transformer ⇔ control unit): 150 cm
CAUTION
Risk of 󹪝r
e
The transformer housing temperature can rise to over 105 °C in the event of a fault in the
controller or a short circuit in the output line of the transformer.
As a result, you should take the following safety measures:
Only mount the transformer on surfaces with no risk of ignition, and which cannot be
touched by unauthorized persons.
Inform the service personnel about the risk of 󹪝re.
NOTICE
Use the SIDOOR Transformer UL indoors only.
Power supply
7.3 SIDOOR TRANSFORMER UL
ATD4xxW for industrial applications
System Manual, 06/2022, A5E51901827B AA 251