On the output side, the switch mode power supply supplies a 36 V DC (± 3 %) SELV at a rated
output power < 100 W. The device can brie󹪞y (< 2 s) deliver a 15 A current to enable fast
acceleration (corresponds to a brief power output of 540 W).
Short-circuit protection
Output X2 is short-circuit proof.
LED display
LED L1 indicates the presence of the output voltage.
Note
If the LED does not light up despite being correctly connected to the X1 supply line and if there
is no measurable output voltage, this indicates a short circuit on the output side or a defective
module!
The device can be operated by the control unit without load to establish whether the module is
defective. If the LED at the output does not light up in this mode of operation, and there is no
measurable voltage at the output, this indicates that the device is defective!
See also
Controllers (Page 33)
7.1.2 Installation
Requirements
Observe the following installation rules:
Minimum clearance to surrounding parts: 1 cm
Even mounting surface
The installation point should, as far as possible, be vibration-free. The permissible climatic
conditions (operation or storage and transport temperature) must be adhered to
(see Technical data (Page 240)).
Maximum distance to power supply depending on cable length:
Connecting cable input line (mains ⇔ NT40): 200 cm
Connecting cable output line (NT40 ⇔ control unit): 150 cm
Operation outside the speci󹪝ed temperature range can lead to danger, malfunctions and
failure of the equipment.
Protection class I
The device must be installed in places that are accessible only to quali󹪝ed personnel.
Power supply
7.1 SIDOOR NT40
ATD4xxW for industrial applications
236 System Manual, 06/2022, A5E51901827B AA