Weight to 
be moved
[kg]
Energy [J]
4 10 25 50 75 100
550 121 191 302 426 522 603
600 115 183 289 408 500 577
Parameter assignment
The determination of the values for the energy limit is performed using the following 
parameters:
• In closing direction: p1202
• In opening direction: p1203
• NDG mode: p1204
Parameter assignment is possible via the driving parameters or the terminal module.
If an energy limitation parameter is set to 0, the speed limitation is suppressed in accordance 
with the kinetic energy.
4.2.8 External closing force
Description of function
WARNING
Risk of injury due to moving mechanical parts
Make sure that with an additional external closing force the sum of external closing force and 
force set in the controller does not exceed the maximum force limit of 150 N (according to EN 
ISO 14120:2015).
Check the nal application-specic limit values and adjust the limit values accordingly.
4.2.9 Synchronization of the door position
Description of function
The determined door position is set to zero when a blocking of the door in the area of 1 cm before 
the minimally reached CLOSED position has been detected or if the door position is below the 
minimally reached CLOSED position.
As of V1.09: The determined door position is set to zero when the CLOSED position is reached. 
If the last reached OPEN position is larger than the door width plus 1 cm which was determined 
during the learn run or if the door position is below the minimally reached CLOSED position.
SIDOOR functions
4.2 System functions
ATD4xxW for industrial applications
76 System Manual, 06/2022, A5E51901827B AA