RoHS Directive
(RoHS = Restrictions of the use of certain Harzardous Substances)
2011/95/EU "Restriction of the use of certain hazardous substances in electrical and electronic
equipment"
According to the requirements of EN 50581, the product does not contain any dangerous
substances.
12.1.1.2 ATEX Approval
Table 12-1 ATEX Certification
Type examination certificate
(number)
DEKRA 17ATEX0047 X
Standards
EN 60079-0
EN 60079-7
EN 60079-11
EN 60079-15
EN 60079-31
Type: 6ES7655-5PX11-1XX0
II 3 (3)
GD
Ex ec [ic Gc] [ic IIIC Dc] IIC T4 Gc
and
II 3 (3)
GD
Ex nA [ic Gc] [ic IIIC Dc] IIC T4 Gc
Type: 6ES7655-5PX11-1AX0
II 3 G Ex ec [ic] IIC T4 Gc
and
II 3 D Ex tc [ic] IIIC T80 °C Dc
WARNING
Personal injury and material damage can be incurred.
In potentially explosive atmospheres, personal injury and material damage can be incurred if
plug connections are disconnected during operation.
Read section "Use in hazardous areas (Page 29)".
Technical specifications
12.1 General technical specifications
SIMATIC CFU
Commissioning Manual, 08/2019, A5E39252870-AD 149