4.6 CFU PA: Voltage relationships (galvanic isolation)
The CFU PA has galvanic isolation between the fieldbus and all other circuit components of the
CFU PA.
4.7 CFU PA: Functions of the fieldbus connections (FB)
FIELDBUS
The CFU PA compiles the protocols between the PROFINET IO and the PROFIBUS PA.
With regard to field devices, the CFU PA operates like a BusLink (PROFINET IO to PROFIBUS
PA) with connected field distributors for PA field devices.
You connect the PA field devices to the "FIELDBUS; FB<n>" connections on the CFU PA. CFU
PA and PA field devices form a common autonomous PROFIBUS PA system.
Parameters
Information on parameter assignment of the field devices can be found in the documentation of
the field device.
Availability
For the "FIELDBUS; FB<n>" connections, the following applies when physical faults occur
(such as wire break or short circuit):
Faulty connections are automatically deactivated as long as the fault exists.
The bus is automatically terminated
Repairs and extensions at the individual "FIELDBUS; FB<n>" connections are possible
during operation.
Additional information
Section "CFU PA: Voltage relationships (galvanic isolation) (Page 28)"
Section "Diagnostics via LED displays (Page 107)"
Section "CFU PA: Using service interface (Page 124)"
You can find information on configuring and assigning parameters in section
"Commissioning (offline) (Page 83)".
4.8 System change during operation
During operation of the CFU, you can carry out the following functions:
Adding components
Replacing components
Operation planning
4.8 System change during operation
SIMATIC CFU
28 Commissioning Manual, 08/2019, A5E39252870-AD

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simatic CFU and is the answer not in the manual?

Siemens Simatic CFU Specifications

General IconGeneral
BrandSiemens
ModelSimatic CFU
CategoryI/O Systems
LanguageEnglish

Related product manuals