11.3 Configuration with SIMATIC CFU with aluminum housing
11.3.1 Introduction
Figure 11-2 Example: SIMATIC CFU PA Bundle in aluminum housing (here without housing cover)
Housing configuration
The housing is made of impact-resistant, powder-coated die-cast aluminum AlSi12. It consists
of a base and a cover. It is dustproof and waterproof according to protection class IP 66.
Installing cables in the housing
Observe the installation regulations during installation in accordance with EN 60079‑14.
The SIMATIC CFU with aluminum housing contains cable glands with an M20x1.5 thread
for cable diameters from 7 mm to 13 mm (with a reducing insert: cable 4 mm to 8 mm)
It is possible to install specially certified cable and conductor glands, as well as blanking and
sealing plugs.
Compact Field Unit in the housing for use in a hazardous area
11.3 Configuration with SIMATIC CFU with aluminum housing
SIMATIC CFU
132 Commissioning Manual, 08/2019, A5E39252870-AD