4. Position the objects according to the order of the cables in the system.
Note
You can move the displayed objects. You can use the miniature view to select the section
to be displayed.
5. Using drag-and-drop, connect the connections of the CPU, the CFU and other components
on the PROFINET IO system (green rectangles) according to the order of the cables in the
system.
On the "Table view" tab, you can make other system-specific settings (e.g. lengths of
cables).
You can find additional information about this in the online help of the dialog box.
Additional information
STEP 7 online help
8.6.4 Assigning the CFU parameters without configuration
Requirement
The device name must be unique in the PROFINET IO system.
The programming device interface must be connected directly to the PROFINET IO system.
The MAC address of the CFU is known.
SIMATIC PDM is used for parameter assignment.
Commissioning
8.6 Preparing the CFU for commissioning
SIMATIC CFU
80 Commissioning Manual, 08/2019, A5E39252870-AD