Adapt inputs and outputs
SINAMICS G110M Operating Instructions
118 Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
Flying restart enable signal source
p0855 Unconditionally release holding brake p2103 1. Acknowledge faults
p0858 Unconditionally close holding brake p2112 External alarm 1
Fixed speed setpoint selection bit 0
Technology controller enable
p1021 Fixed speed setpoint selection bit 1 p3330 Two-wire/three-wire control, control
p1022 Fixed speed setpoint selection bit 2 p3331 Two-wire/three-wire control, control
p1023 Fixed speed setpoint selection bit 3 p3332 Two-wire/three-wire control, control
Motorized potentiometer, setpoint, raise
A complete list of the binector outputs is provided in the List Manual.
Changing the function of a digital input - example
he motor with digital input DI 2,
you have to connect the status parameter of DI
2 to
p0840: Set p0840 = 722.2.
You can debounce the digital input signal using parameter p0724.
For more information, see the parameter list and the function block diagrams 2210 ff of the
List Manual.
Analog inputs as digital inputs
When required, you can use the analog inputs as additional digital inputs.
Figure 6-2 Additional digital inputs