SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
117
Adapt inputs and outputs
6
This chapter describes how you adapt the function of individual digital and analog inputs and
outputs of the inverter.
See also
Interconnecting signals in the inverter (Page 321)
Deadband of the analog inputs (Page 123)
Commissioning (Page 83)
Figure 6-1 Internal interconnection of the inputs and outputs
Digital inputs
Changing the function of the digital input
Interconnect the status parameter of the digital input with a bi-
nector input of your choice.
Binector inputs are marked with "BI" in the parameter list of the List
Manual.
Table 6- 1 Binector inputs (BI) of the inverter (selection)
BI
Significance
BI
Significance
p0810
Command data set selection CDS bit 0
p1036
Motorized potentiometer, setpoint, lower
p0840 ON/OFF1 p1055 Jog bit 0
p0844
OFF2
p1056
Jog bit 1
p0848
OFF3
p1113
Setpoint inversion