Functions
8.4 Setpoint sources
SINAMICS G110M Operating Instructions
170 Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
Under the following conditions, the inverter switches from the main setpoint to other
setpoints:
When the technology controller is active and appropriately interconnected, its output
specifies the motor speed.
When jogging is active.
When controlling from an operator panel or the STARTER PC tool.
8.4.1
Analog input as setpoint source
Interconnecting an analog input
If you have selected a pre-assignment without a function of the analog input, then you must
interconnect the parameter of the main setpoint with an analog input.
Figure 8-8 Example: Analog input 0 as setpoint source
Table 8- 1 Setting with analog input 0 as setpoint source
Parameter
Remark
p1070 = 755[0]
Main setpoint
Interconnect the main setpoint with analog input 0
p1075 = 755[0]
Additional setpoint
Interconnect the additional setpoint with analog input 0
You must adapt the analog input to the connected signal, e.g. ± 10 V or 4 20 mA. You will
find additional information in the section: Analog inputs (Page 120).
8.4.2
Specifying the motor speed via the fieldbus
If you enter the setpoint via a fieldbus, you must connect the converter to a higher-level
control. For further information, see Section Configure fieldbus (Page 125).