Configure fieldbus
7.5 Communications via AS-i
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
147
● Default setting 32 - Single Slave mode, modified addressing :
Single Slave mode with "ON clockwise / OFF1", "ON counter-clockwise / OFF1", speed
setpoint via CDS0 or CDS1
● Default setting 34 - Dual Slave mode with "ON/OFF1", "OFF2"
Dual Slave mode with "ON/OFF1", "OFF2", speed setpoint via control
Details about the default settings are contained in the operating instructions of your inverter,
see Inverter factory setting (Page 87)
The following table shows the AS-i plug assignment. Further connection information is
contained in the AS-Interface system manual, see AS-i System Interface Manual
(https://support.industry.siemens.com/cs/gb/en/view/1171856)
Table 7- 8 Pin assignment
X03 AS-i,
(M12, IP57)
Pin Function Description
2 0 V Reference potential for terminal 4
As factory setting, all AS-i slaves have address 0. Slaves with address 0 are not included in
the communication.
The addresses must be unique, although they can be mixed as required.
You have the following options when making the address assignment:
● Automatic addressing via the AS-i master
● Addressing via the addressing device
● Addressing via parameters
Before you set the address, you must specify whether the inverter is integrated as Single
Slave or Dual Slave in the AS-i network.
● p2013 = 0: Single Slave (factory setting)
● p2013 = 2: Dual Slave