Default setting 32 - Single Slave mode, modified addressing :
Single Slave mode with "ON clockwise / OFF1", "ON counter-clockwise / OFF1", speed
setpoint via CDS0 or CDS1
Default setting 34 - Dual Slave mode with "ON/OFF1", "OFF2"
Dual Slave mode with "ON/OFF1", "OFF2", speed setpoint via control
Details about the default settings are contained in the operating instructions of your inverter,
see Inverter factory setting (Page 87)
Connection
The following table shows the AS-i plug assignment. Further connection information is
contained in the AS-Interface system manual, see AS-i System Interface Manual
(https://support.industry.siemens.com/cs/gb/en/view/1171856)
Table 7- 8 Pin assignment
X03 AS-i,
(M12, IP57)
Pin Function Description
1
AS-i +
AS-i plus signal
2 0 V Reference potential for terminal 4
3
AS-i -
AS-i minus signal
4
24 V
24 V auxiliary voltage
5
Not assigned
7.5.1
Setting the address
As factory setting, all AS-i slaves have address 0. Slaves with address 0 are not included in
the communication.
The addresses must be unique, although they can be mixed as required.
You have the following options when making the address assignment:
Automatic addressing via the AS-i master
Addressing via the addressing device
Addressing via parameters
Before you set the address, you must specify whether the inverter is integrated as Single
Slave or Dual Slave in the AS-i network.
p2013 = 0: Single Slave (factory setting)
p2013 = 2: Dual Slave