EasyManua.ls Logo

Siemens SINAMICS G110M - Control and Status Word 1

Siemens SINAMICS G110M
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configure fieldbus
7.4 PROFIdrive profile for PROFIBUS and PROFINET
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
135
Figure 7-3 Interconnection of the receive words
The telegrams use - with the exception of telegram 999 (free interconnection) - the word-by-
word transfer of send and receive data (r2050/p2051).
If you require an individual telegram for your application (e.g. for transferring double words),
you can adjust one of the predefined telegrams via parameters p0922 and p2079. For
details, please refer to the List Manual, function diagrams 2420 and 2472.
7.4.1.1
Control and status word 1
Control word 1 (STW1)
Bit
Significance
Explanation
Signal inter-
connection
in the in-
verter
Telegram 20
All other tele-
grams
0 0 = OFF1 The motor brakes with the ramp-down time
p1121 of the ramp-function generator. The
inverter switches off the motor at standstill.
p0840[0] =
r2090.0
0 1 = ON The inverter goes into the "ready" state. If, in
addition bit 3 =
1, then the inverter switches on
the motor.
1 0 = OFF2 Switch off the motor immediately, the motor
then coasts down to a standstill.
p0844[0] =
r2090.1
1 = No OFF2 The motor can be switched on (ON com-
mand).