Appendix
A.7 Acceptance tests for the safety functions
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
327
Status
The inverter signals
the following:
"STO selection via
PROFIsafe"
(r9772.20 = 1)
The inverter signals
the following:
"STO Selection via
terminal"
(r9772.17 = 1)
The inverter signals
the following:
"STO Selection via
terminal on Power
Module"
(r9772.25 = 1)
If a mechanical brake is not available, the motor coasts down.
A mechanical brake brakes the motor and holds it to ensure that it remains
at standstill.
The inverter signals neither faults nor alarms of the safety functions
(r0945[07], r2122[07]).
The inverter signals the following:
"STO is selected" (r9773.0 = 1).
"STO is active" (r9773.1 = 1).
4.
Deselect STO
4.1. Deselect STO.
4.2.
Check the following:
STO is not active (r9773.1 = 0).
The inverter signals neither faults nor alarms of the safety functions
(r0945[07], r2122[07]).
You have performed the acceptance test of the STO function.
A.7.2
Machine documentation ((only STO))
Machine or plant description
Designation
Type
Serial number
Manufacturer
End customer
Block diagram of the machine and/or plant: