Configure fieldbus
7.4 PROFIdrive profile for PROFIBUS and PROFINET
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
145
Write request: Assign digital input 2 with the function ON/OFF1 (p0840[1] = 722.2)
In order to link digital input 2 with OFF1/ON, you must assign parameter p0840[1] (source,
ON/OFF1) the value 722.2 (DI 2). To do this, you must fill the telegram of the parameter
channel as follows:
●
PKE, bit 12 … 15 (AK): = 7 hex
(change, parameter value (field, word))
●
PKE, bit 0 … 10 (PNU): = 348 hex
(840 = 348 hex, no offset, as 840 < 1999)
●
IND bit 8 … 15 (subindex): = 1 hex
(CDS1 = index1)
●
IND, bit 0 … 7 (page index): = 0 hex
(offset 0
≙ 0 hex)
●
: =
(722 = 2D2 hex)
●
PWE2, bit 10 … 15: = 3f hex
(drive object - for SINAMICS G120, always 63 = 3f hex)
●
(index of parameter (DI 2 = 2))
Figure 7-5 Telegram, to assign DI 2 with ON/OFF1
Write request: Change restart mode (p1210)
The restart mode is inhibited in the factory setting (p1210 = 0). In order to activate the
automatic restart with "acknowledge all faults and restart for an ON command", p1210 must
be set to 26:
●
PKE, bit 12 … 15 (AK): = 7
(change parameter value (field, word))
●
PKE, bit 0 … 10 (PNU): = 4BA hex
(1210 = 4BA hex, no offset, as 1210 < 1999)
●
IND, bit 8 … 15 (subindex): = 0 hex
(parameter is not indexed)
●
IND, bit 0 … 7 (page index): = 0 hex
(offset 0
corresponds to 0 hex)
●
PWE1, bit 0 … 15: = 0 hex
●
PWE2, bit 0 … 15: = 1A hex
(26 = 1A hex)
Figure 7-6 Telegram, to activate the automatic restart with p1210 = 26
Slave-to-slave communication
"Direct data exchange" is sometimes called "slave-to-slave communication" or "data
exchange broadcast". Here, slaves exchange data without any direct involvement of the
master.