Configure fieldbus
7.3 Communication via PROFIBUS
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
131
NOTICE
External 24 V power supply must be disconnected
The external 24 V power supply must be switched off before the DIP switch settings are
changed. DIP switch setting changes do not take effect until the Control Unit has been
powered-up again.
Setting the PROFIBUS DP address via DIP switches
The PROFIBUS DP address can be set via DIP switch, as shown in the table below.
Table 7- 1 Example address for the PROFIBUS DP interface
DIP switch
1
2
3
4
5
6
7
Add to address
1
2
4
8
16
32
64
Example 1: Address = 3 = 1 + 2
Example 2: Address = 88 = 8 + 16 + 64
7.3.5
Select telegram
Precondition
In the basic commissioning, you have selected a setting with fieldbus.
See also Section: Basic commissioning (Page 84).
Procedure
Proceed as follows to set a specific telegram in the inverter:
Using STARTER or an operator panel, set parameter p0922 to the appropriate value.
You have set a specific telegram in the inverter.