EasyManua.ls Logo

Siemens SINAMICS G110M - Pulse Frequency and Current Reduction

Siemens SINAMICS G110M
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
12.6 Pulse frequency and current reduction
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
309
12.6
Pulse frequency and current reduction
Relationship between pulse frequency and output base-load current reduction
Table 12- 7 Current reduction depending on pulse frequency
1
Rated power
based on LO
Rated output current at pulse frequency of
4 kHz
6 kHz
8 kHz
10 kHz
12 kHz
14 kHz
16 kHz
0.37 kW
1.30 A
1.11 A
0.91 A
0.78 A
0.65 A
0.59 A
0.52 A
0.75 kW
2.2 A
1.9 A
1.5 A
1.3 A
1.1 A
1.0 A
0.9 A
1.1 kW
3.1 A
2.6 A
2.2 A
1.9 A
1.6 A
1.4 A
1.2 A
1.5 kW
4.1 A
3.5 A
2.9 A
2.5 A
2.1 A
1.8 A
1.6 A
2.2 kW
5.6 A
4.8 A
3.9 A
3.4 A
2.8 A
2.5 A
2.2 A
3.0 kW
7.3 A
6.2 A
5.1 A
4.4 A
3.7 A
3.3 A
2.9 A
4.0 kW 8.8 A 7.5 A 6.2 A 5.3 A 4.4 A 4.0 A 3.5 A
1
The permissible motor cable length depends on the cable type and the chosen pulse frequency.

Table of Contents