EasyManua.ls Logo

Siemens SINAMICS G110M - Load Monitoring

Siemens SINAMICS G110M
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
8.9 Application-specific functions
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
237
Stall protection
Principle of operation
If the speed lies below the value of p2175 for the time set in p2177, and the converter is
operating at the current or torque limit, using bit 6 of status word 2 for monitoring functions
(r2198.6), the converter outputs the "Motor blockedmessage.
The converter goes to the current or torque limit if the setpoint speed is significantly higher
than the actual speed.
Applications: Extruders and mixers
Settings
Parameters
Description
p2175
Motor blocked speed threshold (
factory setting: 120 rpm)
p2175 = 0: Blocking protection deactivated
p2177
Motor blocked delay time (factory setting: 3 s)
Stall protection
Principle of operation
If the value in r1746 exceeds the value of p1745 for the time set in p2178, using bits 7 of
status word 2, for monitoring functions (r2198.7) the converter outputs the "Motor stalled"
message.
Applications: General system protection
Settings
Parameters
Description
p1745
Motor model fault threshold value stall detection (
factory setting: 5 %)
If the motor stalls too early with this setting, then using the trace function you have
the option of determining a better value. To do this, set p1745 = 100.
p2178
Motor stalled delay time (factory setting: 0.01 s)
8.9.7.2
Load monitoring
The load monitoring comprises the following components:
Load failure monitoring
Monitoring for torque deviation
Pump monitoring
Fan monitoring
If the load monitoring detects load failure, then the converter always goes into a fault
condition and outputs fault F07936. For a torque and speed deviation, as response, you can
either set an alarm or a fault. Details are provided in the following descriptions.

Table of Contents

Other manuals for Siemens SINAMICS G110M

Related product manuals