Configure fieldbus
7.2 Communication via PROFINET
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
127
Further information on PROFINET can be found on the Internet using the following links:
– General information about PROFINET can be found at Industrial Communication
(http://support.automation.siemens.com/WW/view/en/19292127).
– The configuration of the functions is described in the PROFINET system description
(http://www.automation.siemens.com/mcms/automation/en/industrial-
communications/profinet/Pages/Default.aspx) manual.
What do you need for communication via PROFINET?
Check the communication settings using the following table. If you answer "Yes" to the
questions, you have correctly set the communication settings and can control the converter
via the fieldbus.
Is the inverter correctly connected to
See: Connect the converter to
Do the IP address and device name
in the converter and controller
See Configuring communication
to the control (Page 128)
See manuals for your
inverter, fieldbus commu-
nication manual
(Page 334)
Is the same telegram set in the con-
verter as in the higher-level control-
Set the telegram in the convert-
er, see: Select telegram
Are the signals that the converter
and the controller exchange via
PROFINET correctly interconnected?
PROFIdrive-compliant intercon-
nection in the converter, see:
PROFIdrive profile for
PROFIBUS and PROFINET
Connect the converter to PROFINET
Procedure
To connect the inverter to a control via PROFINET, proceed as follows:
1. Integrate the inverter in the bus system (e.g. ring topology) of the control using
PROFINET cables and the two PROFINET sockets X150-P1 and X150-P2.
The position of the sockets and the pin assignment can be found in Section Connection
and cables (Page 63).
The maximum permitted cable length from the previous station and to the subsequent
one is 100 m.
2. Externally supply the inverter with 24 V DC through terminals 31 and 32.
The external 24 V supply is only required if communications with the control should also
run when the mains voltage is switched off.
You have connected the inverter to the control using PROFINET.