Configure fieldbus
7.4 PROFIdrive profile for PROFIBUS and PROFINET
SINAMICS G110M Operating Instructions
138 Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
Control and status word 3
The control and status words fulfill the specifications of PROFIdrive profile version 4.1 for the
"closed-loop speed controlled" mode.
Control word 3 has the following default assignment. You can change the signal
interconnection.
Signal interconnection
in the inverter
1)
0 1 Fixed setpoint, bit 0 Selects up to 16 different fixed setpoints. p1020[0] = r2093.0
Changes over between settings for differ-
ent motors (drive data sets).
6 – Not used
Technology controller enable
Enable or inhibit speed controller droop.
12
Changes over the control mode for vector
control.
p1501[0] = r2093.12
Closed-loop speed control active
13
-- p2106[0] = r2093.13
External fault is active (F07860)
15 1 CDS bit 1 Changes over between settings for differ-
ent operation interfaces (command data
p0811[0] = r2093.15
If you switch from telegram 350 to a different one, then the inverter sets all interconnections p1020, … to "0". Exception: