Technical data
12.3 SINAMICS G110M specifications
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
305
SINAMICS G110M specifications
Power Module Specifications
Note
UL certified Fuses must be used
UL certified Fuses must be used" it should state "In order that the system is in compliance
with UL requirements, UL listed class J fuses must be used. The fuse rating of these fuses
must be equal to or less that the ratings given in
Table 4-2 Rated Output, Input and Fuses
57).
IP protection of the system
The Power Module and the Terminal Unit (which includes the Control Module) when fully
assemble
d and attach to the motor has an IP rating of IP65/66 depending on the version of
Minimum required resistance for the braking resistors
For each Power Module rating there is a minimum resistance required for the braking
resistors associated with the specific power modules, please see the table below for further
details.
Table 12- 3 PM240M Power Modules - minimum resistance for braking resistors
Minimum resistance for
braking resistors
based on High Overload (HO)
FSA 0.37 1.3 6SL3517-1BE11-
200 Ω
FSA 0.75 2.2 6SL3517-1BE12-
200 Ω
FSA 1.1 3.1 6SL3517-1BE13-
200 Ω
FSA 1.5 4.1 6SL3517-1BE14-
200 Ω
FSB 2.2 5.6 6SL3517-1BE16-
60 Ω
FSB 3.0 7.3 6SL3517-1BE17-
60 Ω
FSB 4.0 8.8 6SL3517-1BE21-
0AM0
60 Ω