Configure fieldbus
7.5 Communications via AS-i
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
149
If you assign the address via STARTER, you must save the settings via (RAM -> ROM).
● Address range for Single Slave inverter, profile 7.F.E
– p2012[1]: 0 … 31, range for A address, 0A … 31A
● Address range for Dual Slave inverter, profile 7.A.5 or 7.A.E
– p2012[0]: 0 … 31, 33 … 63 for slave 1
– p2012[1]: 0 … 31, 33 … 63 for slave 2
with
– 0 … 31 range for A address, 0A … 31A
– 33 … 63 range for B address, 1B … 31B
In Single Slave mode, four bits are available for the communication between the AS-i master
and the inverter. The four bits are used to transfer process data. In parallel, the control can
start a diagnostic request via AS-i.P0.
The following default settings are available; both work with profile 7.F.E.
● Default setting 30: Standard Single Slave mode
● Default setting 32: Modified Single Slave mode
Default setting 30: Standard Single Slave mode
In standard addressing, the control specifies the speed setpoint via the motor control bits
(AS-i.DO0 … AS-i.DO3).
AS-i.DO0
>
AS-i.DO1
>
AS-i.DO2
>
= 2093.2
AS-i.DO3
>
= 2093.3
For details, see AS-i System Interface Manual
(https://support.industry.siemens.com/cs/gb/en/view/1171856).
If the control specifies the speed setpoint, the inverter replies:
p2080[0] = 53.13
>
-i.DI0
Operational enable for PLC
p2080[1] = 899.11
>
-i.DI1
p2080[2] = 722.0
>
-i.DI2