7.5 Communications via AS-i
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
149
If you assign the address via STARTER, you must save the settings via (RAM -> ROM).
Address range for Single Slave inverter, profile 7.F.E
p2012[1]: 0 … 31, range for A address, 0A31A
Address range for Dual Slave inverter, profile 7.A.5 or 7.A.E
p2012[0]: 0 … 31, 3363 for slave 1
p2012[1]: 0 … 31, 3363 for slave 2
with
031 range for A address, 0A 31A
3363 range for B address, 1B31B
7.5.2
Single slave mode
In Single Slave mode, four bits are available for the communication between the AS-i master
and the inverter. The four bits are used to transfer process data. In parallel, the control can
start a diagnostic request via AS-i.P0.
The following default settings are available; both work with profile 7.F.E.
Default setting 30: Standard Single Slave mode
Default setting 32: Modified Single Slave mode
Default setting 30: Standard Single Slave mode
In standard addressing, the control specifies the speed setpoint via the motor control bits
(AS-i.DO0 AS-i.DO3).
Control -> inverter
AS-i.DO0
-
>
p1020 = 2093.0
Fixed speed bit 0
AS-i.DO1
-
>
p1021 = 2093.1
Fixed speed bit 1
AS-i.DO2
-
>
p1022
= 2093.2
Fixed speed bit 2
AS-i.DO3
-
>
p1023
= 2093.3
Fixed speed bit 3
For details, see AS-i System Interface Manual
(https://support.industry.siemens.com/cs/gb/en/view/1171856).
Inverter -> control
If the control specifies the speed setpoint, the inverter replies:
p2080[0] = 53.13
-
>
AS
-i.DI0
Operational enable for PLC
p2080[1] = 899.11
-
>
AS
-i.DI1
Pulses enabled
p2080[2] = 722.0
-
>
AS
-i.DI2
State DI0