Installation
4.3 Electrical Installation
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
73
4.3.4
Cable protection
Cable protection for individual converters
If you individually protect an Inverter, then you must protect the Inverter feeder cable using a
fuse.
Table 4- 6 Individual fuse protection
Rated power
Power Module
Frame size
Fuse
0.37 kW
6SL3517-1BE11-3AM0
FSA
10 A
3NA3803
0.75 kW 6SL3517-1BE12-3AM0 FSA 10 A 3NA3803
1.1 kW
6SL3517-1BE13-3AM0
FSA
10 A
3NA3803
1.5 kW 6SL3517-1BE14-3AM0 FSA 10 A 3NA3803
2.2 kW
6SL3517-1BE16-3AM0
FSB
20 A
3NA3807
3 kW
6SL3517-1BE17-3AM0
FSB
20 A
3NA3807
4 kW
6SL3517-1BE21-3AM0
FSB
20 A
3NA3807
For additional information, please refer to Catalog D31at the following link:
SINAMICS and motors for Single-Axis Drives D31 catalog
(https://intranet.automation.siemens.com/mcms/infocenter/content/en/Pages/order_form.asp
x?nodeKey=key_566000&infotype=catalogs&linkit=null)
Installation using power-through daisy chain
The SINAMICS G110M system has been designed to allow a converter to utilize power-
through to provide the mains power for a number of converters in a daisy chain.
The maximum current limits for the daisy chain are given below:
For the HanQ variants the maximum current of the daisy chained converters must not
exceed 16 A.
For the Glanded variants the maximum current on the daisy chained converters must not
exceed 12 A.
For both HanQ and Glanded variants the input for the daisy chained converters can be
protected by a 20 A fuse.
It is the users responsibility to ensure that the current limits are not exceeded.