Commissioning
5.2 Basic commissioning
SINAMICS G110M Operating Instructions
98 Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
5.2.5
Basic commissioning with IOP
Basic commissioning wizard
1.
Select "Basic Commissioning...
" from the Wizards
menu.
2.
Select "Yes
" or "
No
" to a factory reset.
It is recommended that a factory reset is performed to
ensure that the converter is in a known and stable state
prior to commissioning.
Once "Yes
" is selected the IOP will initiate a factory
reset immediately.
3.
On completion of the factory reset the
"
Application
Class
" is selected.
In this example the "Standard Drive Control" is selected.
4.
Select the correct Motor Data for your Inverter and a
t-
tached motor.
This data is used to calculate the correct speed and
displayed values for the application.