Functions
8.7 Protection functions
SINAMICS G110M Operating Instructions
200 Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
Commissioning the torque control
The torque control only functions error-free if, during the basic commissioning, you correctly
set the motor data and performed the motor data identification with the motor in the cold
state.
See also section: Basic commissioning with IOP (Page 98).
Table 8- 14 The most important torque control parameters
p1300
22: Torque control without speed encoder
p0300 …
p0360
is transferred from the rating plate during basic commissioning and calcu-
lated with the motor data identification
Additional information about this function is provided in the parameter list and in function
diagrams 6030 onwards in the List Manual.
The frequency inverter offers protective functions against overtemperature and overcurrent
for both the frequency inverter as well as the motor. Further, the frequency inverter protects
itself against an excessively high DC link voltage when the motor is regenerating.
Inverter temperature monitoring
The inverter temperature is essentially defined by the following effects:
● The ambient temperature
● The ohmic losses increasing with the output current
● Switching losses increasing with the pulse frequency
The inverter monitors its temperature using the following monitoring types:
● I
2
t monitoring (alarm A07805, fault F30005)
● Measuring the chip temperature of the Power Module (alarm A05006, fault F30024)
● Measuring the heat sink temperature of the Power Module (alarm A05000, fault F30004)