Functions
8.10 Safe Torque Off (STO) safety function
SINAMICS G110M Operating Instructions
248 Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
8.10.3.4
Configuring safety functions
Procedure with STARTER
To configure the safety functions, proceed as follows:
1. Go online.
2. Select the "Safety Integrated" function
3. Select "Change settings".
4. Selecting "STO via terminal":
You have completed the following commissioning steps:
You have started to commission the safety functions.
You have selected the basic functions with control via onboard terminals of the inverter.
The other selection options are described in the "Safety Integrated Function Manual". See
also section: Manuals for your converter (Page 334).
8.10.3.5
Interconnecting the "STO active" signal
If you require the feedback signal "STO active" of the inverter in your higher-level control
system, then you must appropriately interconnect the signal.
Precondition
You are online with STARTER or Startdrive.