Commissioning
5.2 Basic commissioning
SINAMICS G110M Operating Instructions
92 Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
Action 2 (no motor codes):
1. If 1 is entered (Induction motor), the IOP will automatically set p0301 to 0.
2. The basic commissioning wizard continues and asks for the relevant motor data to be
entered during the commissioning process.
5.2.3
Restoring the factory settings
Sometimes there are cases when the commissioning of the converter goes wrong, for
example:
The line voltage was interrupted during commissioning and the commissioning process
could not be completed.
The user was interrupted during the commissioning process and could not remember
what parameters had been changed.
You do not know whether the converter was already operational.
In cases such as these, resetting the converter to the factory settings is accomplished by
setting the following parameters to the shown values:
Parameter p0010=30.
Parameter p0970 = 1.