Commissioning
5.2 Basic commissioning
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
91
1LE1 4.00 12023
When the relevant motor code is entered, the motor data automatically assigned for the
selected motor. The user can then complete the commissioning process without the need to
perform a motor ID.
Commissioning without using motor codes
When commissioning the system without using motor codes, the following steps must be
performed, otherwise the motor will not be commissioned correctly.
1. Set p0010 = 1 (Enter the quick commissioning mode).
2. Set p0300 = 1 (Induction motor [rotating]).
3. Set p0301 = 0 (This disables the automatic motor data assignment).
4. Complete the commissioning process, entering the motor data (from the motor rating
label) into the relevant parameters.
5. Set p3900 = 1, 2 or 3 to end quick commissioning, depending on the users requirements.
Parameter p0301 must be set to 0
When commissioning using the manual input of motor data, it is important that p0301 is set
to 0.
If p0301 is not set to 0, then even if the motor ID function is selected at the completion of
the commissioning process, no motor ID will actually be performed. If the motor ID is not
performed it could leave the motor in an unpredictable state and that may adversely affect
the users application.
Therefore, it is essential that p0301 is checked to ensure it is actually set to 0.
Commissioning with the Intelligent Operator Panel (IOP)
When using the basic commissioning wizard on the IOP the user will presented with a
screen asking for the motor type (p0300) to be entered. Depending on the value that is input
into the IOP, there are two different branches to the commissioning wizard.
Action 1(using motor codes):
1. If 100 or 177 is entered, the user is then presented with the motor code screen (p0301).
2. Entered the relevant code for the motor.
3. The motor data is automatically assigned for the motor.
4. The basic commissioning wizard continues but does not ask for any further motor data to
be entered.