Functions
8.4 Setpoint sources
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
171
Interconnecting the fieldbus with the main setpoint
Figure 8-9 Fieldbus as setpoint source
Most standard telegrams receive the speed setpoint as a second process data PZD2.
Table 8- 2 Setting the fieldbus as setpoint source
Parameter
Remark
p1070 = 2050[1]
Main setpoint
Interconnect the main setpoint with process data PZD2 from the fieldbus.
p1075 = 2050[1]
Additional setpoint
Interconnect the additional setpoint with process data PZD2 from the fieldbus.
8.4.3
Electromechanical potentiometer
The SINAMICS PM240M power module has a perm
a-
nently hardwired electromechanical
potentiometer.
The potentiometer is permanently active and is, by d
e-
fault the main setpoint source.
When the main setpoint source is set to fieldbus, for e
x-
ample when using PROFIBUS or PROFINET commun
i-
cations, the potentiometer is disabled.
The default set
ting for the electromechanical potentiome-
ter is Unipolar voltage input (0 V ... +3 V).
Note
Parameters related to parameter p0756 modification
When changing p0756 , the parameters of the scaling characteristic (p0757, p0758, p0759,
p0760) are overwritten with the following default values:
For p0756 = 0, 1, 4, p0757 is set to 0.0
V, p0758 = 0.0 %, p0759 = 10.0 V and p0760 =
100.0
%.
For p0756 = 2, p0757 is set to 0.0
mA, p0758 = 0.0 %, p0759 = 20.0 mA and p0760 =
100.0
%.
For p0756 = 3, p0757 is set to 4.0
mA, p0758 = 0.0 %, p0759 = 20.0 mA and p0760 =
100.0
%.