Appendix
A.9 Electromagnetic Compatibility
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
331
Siemens plc operates a quality management system, which complies with
the requirements of ISO 9001.
Certificates can be downloaded from the internet under the following link:
Standards (http://support.automation.siemens.com/WW/view/en/22339653/134200)
Electromagnetic Compatibility
The SINAMICS G110M drives have been tested in accordance with the EMC Product
Standard EN 61800-3:2004.
Details see declaration of conformity
Note
Install all drives in accordance with the manufacturer
’s guidelines and in accordance with
Table A- 15 Compliance Table
Category C2 - First Environment - Professional Use
6SL3517-1BE11-*
*0
6SL3517-1BE12-*
*0
6SL3517-1BE13-*
*0
6SL3517-1BE14-*
*0
6SL3517-1BE16-*
*0
6SL3517-1BE17-*
*0
6SL351701BE21-*
*0
All inverters with integrated Class A filters.
The inverter meets the requirements for category C2 for conducted emis-
sions.
In a domestic environment this product may cause radio interference in
which case supplementary mitigation measures may be required.
Note
Install all drives in accordance with the manufacturer
’s guidelines and in accordance with
Use screened cable type CY. The maximum cable length is 15
m, at a switching frequency