Table A- 16 Conducted disturbance voltage and radiated emissions
EMC Phenomenon
Converter type
Remark
Level acc. to
IEC 61800-3
Conducted emissions
(disturbance voltage)
All converters with integrated class A filters.
Order number:
6SL3517-1BE**-*A**
Category C2
First Environment -
Professional Use
Radiated emissions Converter frame sizes A and B with integrated class A
filter.
Order number:
6SL3517-1BE11-*
A
*0
6SL3517-1BE12-*
A
*0
6SL3517-1BE13-*
A
*0
6SL3517-1BE14-*
A
*0
6SL3517-1BE16-*
A
*0
6SL3517-1BE17-*
A
*0
6SL3517-1BE21-*
A
*0
In a domestic environment this product may cause
radio interference in which case supplementary miti-
gation measures may be required.
Category C2
First Environment -
Professional Use
Harmonic Currents
Table A- 17 Harmonic Currents
Typical Harmonic Current (% of rated input current) at U
K
1 %
5th
7th
11th
13th
17th
19th
23rd
25th
24
11
9
7
6
5
4
4
Note
Units installed within the category
C2 (domestic) environment require supply authority
acceptance for connection to the public low
-voltage power supply network. Please contact
your local supply network provider.
Units installed within the category C3 (industrial) environment do not require connection
approval.