Commissioning
5.2 Basic commissioning
SINAMICS G110M Operating Instructions
100 Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
15.
A summary of all the set
tings are displayed.
If the settings are correct, select continue.
16.
The final screens gives two options:
Save settings
Cancel Wizard
If the save option is selected, the settings are saved to
the converter memory. The location of the saved data is
assigned using the "Parameter
Saving
Mode" function in
"Parameter
Settings
" in "
Menu
".
5.2.6
p0015 Macros
Macros for the CU240M
The macros that are available for the CU240M Control Modules are shown in the figures
below. Macro 7 is the default setting for the CU240M DP and CU240M PN Control Modules,
Macro 21 is the default settings for the CU240M USS Control Module and Macro 30 is the
default settings for the CU240M ASi Control Modules.
Figure 5-9 Macro 7 - Switch over between fieldbus and jogging using DI 3 (default DP/PN)