Functions
8.5 Setpoint calculation
SINAMICS G110M Operating Instructions
176 Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
8.5
Setpoint calculation
8.5.1
Overview of setpoint processing
The setpoint can be modified as follows using the setpoint processing:
Invert setpoint to reverse the motor direction of rotation (reversing).
Inhibit positive or negative direction of rotation, e.g. for conveyor belts, pumps or fans.
Skip frequency bands to prevent mechanical resonance effects.
The skip frequency band at speed = 0 results in a minimum speed after switching on the
motor.
Limit to a maximum speed to protect the motor and mechanical system.
Ramp-function generator to accelerate and brake the motor with an optimum torque.
Figure 8-15 Setpoint processing in the converter
8.5.2
Invert setpoint
Procedure
Interconnect parameter p1113 with a binary signal,
e.g. digital input 1.
Table 8- 6 Examples of settings to invert the setpoint
Parameter
Remark
p1113 = 722.1
Setpoint inversion
Digital input 1 = 0: Setpoint remains unchanged.
Digital input 1 = 1: Converter inverts the setpoint.
p1113 = 2090.11
Invert setpoint via control word 1, bit 11.