Adapt inputs and outputs
6.2 Analog inputs
SINAMICS G110M Operating Instructions
122 Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
Table 6- 3 Parameters for the scaling characteristic and wire break monitoring
x-coordinate of 1st characteristic point [V]
p0758
y coordinate of the 1st characteristic point [% of p200x]
p200x are the parameters of the reference variables, e.g. p2000 is the reference
speed.
x-coordinate of 2nd characteristic point [V]
y-coordinate of 2nd characteristic point [% of p200x]
Wire breakage monitoring response threshold
Defining the analog input function
You define the analog input function by interconnecting a connector input of your choice with
parameter p0755 . Parameter p0755 is assigned to the particular analog input via its index,
e.g. parameter p0755[0] is assigned to analog input 0.
Table 6- 4 Connector inputs (CI) of the inverter (selection)
Technology controller setpoint 1
Technology controller actual value
A complete list of the connector inputs is provided in the List Manual.
Defining the analog input function - example
In order to use the analog input AI
0 as the source for
the supplementary setpoint, you h
ave to set
Advanced settings
Signal smoothing
When required, you can smooth the signal, which you read-in via an analog input, using
parameter p0753.
For more information, see the parameter list and in the function block diagrams 9566 ff of the
List Manual.
Small signals of a few millivolts are often corrupted by interference in the cable. To be able
to enter a setpoint of exactly 0 V via an analog input, you must specify a deadband.