Configure fieldbus
7.4 PROFIdrive profile for PROFIBUS and PROFINET
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
143
Know-how protection active, access locked
C8 hex
Change request below the currently valid limit
(change request to a value that lies within
the "absolute" limits, but is however below the currently valid lower limit)
C9 hex
Change request above the currently valid limit
(example: a parameter value is too large for
the inverter power)
CC hex
Change request not permitted
(change is not permitted as the access code is not availa-
Offset and page index of the parameter numbers
Write the parameter number into the PNU (PKE bit 10 ... 0).
≥ 2000
- offset.
Write the parameter number minus the offset into the PNU
(PKE bit
10 … 0).
Write the offset in the page index (IND bit 7 … 0).
6000 … 7999 6000 90 hex 1 0 0 1 0 0 0 0
10000 … 11999 10000 A0 hex 1 0 1 0 0 0 0 0
For indexed parameters, you must write the index as hex value into the subindex (IND
bit 15 … 8).